Sidewalk shed lighting in NYC: the electrical permit and the 2025 lighting standards

Every sidewalk shed requires lighting installed by a licensed electrician under a separate electrical permit. Shed applications filed on or after August 15, 2025 must also meet higher illumination and LED efficiency standards.

Last checked: Oct 23, 2026

Key facts

  • Permit a separate electrical permit, filed in DOB NOW and installed by a licensed electrician
  • Order the lighting is filed and permitted before the shed permit
  • Light level 1.5 foot-candles at the walking surface; 5 within 10 ft of a subway entrance, bus shelter or similar transit facility
  • Fixtures LED, at least 90 lumens per watt, rated to 5°F; adjustable or shielded within 20 ft of dwelling-unit windows
  • Applies to shed applications filed on or after August 15, 2025 (BC 3307.6.4.8; Local Laws 47 and 50 of 2025)

Does a sidewalk shed need an electrical permit?

Yes. Shed lighting must be installed by a licensed electrician under an electrical permit filed separately from the shed permit. For shed applications filed on or after August 15, 2025, BC 3307.6.4.8, as amended by Local Laws 47 and 50 of 2025, requires at least 1.5 foot-candles at the walking surface (5 foot-candles within 10 ft of a subway entrance, bus shelter or similar transit facility), LED fixtures with an efficacy of at least 90 lumens per watt, and shielding of fixtures near dwelling-unit windows.

Key considerations

A separate filing

The shed permit does not cover the lighting. They are two different permits and two different trades.

File the lighting first

DOB’s owner checklist for sidewalk sheds puts the lighting first: the electrical application for the shed lighting must be filed and permitted before the sidewalk shed permit is obtained.

A licensed electrician, always

Shed lighting is not work the general contractor self-performs; it is installed under a licensed electrician’s permit. The work follows the 2025 NYC Electrical Code, in full effect since December 21, 2025.

Higher illumination since August 15, 2025

The minimum at the walking surface rose from 1 foot-candle to 1.5, and to 5 foot-candles within 10 ft of transit entrances and bus shelters.

LED and efficiency

Fixtures must be LED, with a luminous efficacy of at least 90 lumens per watt (previously 45), rated to operate at 5°F and above.

No light trespass into homes

Any fixture within 20 ft of a dwelling unit’s windows must be adjustable or shielded to prevent light trespass into the unit.

Existing sheds

Sheds whose construction documents were filed before August 15, 2025 may keep the previous 1 foot-candle standard, and may be upgraded voluntarily.

Owner-provided sheds

When the owner provides the shed, confirm before the bid whose electrical permit covers the lighting. DOB says only that the electrical permit applies to every sidewalk shed application, not who must hold it.

A frequently omitted line item

Fixtures, circuits, the electrician and the electrical permit are routinely left out of shed pricing. With the 2025 standards, the fixture specification itself has changed.

Checklist: shed lighting

  1. Put the fixtures, circuits, electrician and electrical permit in the shed price.
  2. File the electrical application for the lighting and get it permitted before the shed permit.
  3. Specify LED fixtures of at least 90 lumens per watt, rated to 5°F.
  4. Light the walking surface to 1.5 foot-candles, and to 5 within 10 ft of a transit entrance or bus shelter.
  5. Aim or shield every fixture within 20 ft of an apartment window.
  6. On an owner-provided shed, confirm whose electrical permit covers the lighting.